Alarm Screen
Description &
Classification
(gPOD units
only)
**Urgent
Low CO2
CO2 level is
higher than
alarm set point
(gPOD units
only)
*Warning
VFD Failure
VFD alarm
relay is
energized
Pump-Down
Compressor
failed to Pump-
Down
Exceeded
Maximum Time
or Count
**Urgent
Possible Causes
Incorrect settings
Faulty Sensor
Out of calibration
Co2 level is lower than
normal
Incorrect settings
Faulty Sensor
Loose Connection
Out of calibration
VFD has an alarm
Low or High Pressure
alarm
Suction pressure
remained above
pump-down setpoint
or rose after being
pumped down.
Alarm requires
acknowledgement to
clear
111
Corrective Actions
Check CO2 setpoint
Check CO2 Sensor
Calibrate sensor
Check Co2 Level
Check settings
Check Co2 Sensor
Check Connection and cable
Calibrate sensor
Check VFD's display for alarm or
warning.
When a low or high pressure
alarm occurs, it may cause the
VFD alarm to happen as well.
Resolve this by focusing on the
cause of the Low or High
pressure alarm.
Replace LLSV
Check Suction Pressure Sensor