Data Aire dap4 User Manual page 107

Hide thumbs Also See for dap4:
Table of Contents

Advertisement

Alarm Screen
Description &
Classification
Water Flow
No Water Flow
**Urgent
Floor Water
Senses water
at the floor
Urgent/Critical
Humidity
Humidification
Inhibited
mode is
prohibited from
running
*Warning
Heat Inhibited
Reheat mode
is prohibited
from running
*Warning
Possible Causes
No water flow
Wiring problem
Bad Flow Switch
Incorrect settings on
the controller
Water or moisture
detected on floor
Faulty or damaged
sensor
Faulty Water
Detection Module
Incorrect settings on
the controller
Optional alarm input
switch is configured to
inhibit humidifier
BMS command sent
Unit is in a Zone
Master network that
inhibits humidification
if any unit has recently
been dehumidifying
Optional alarm input
switch is configured to
inhibit reheat
BMS command sent
Unit is in a Zone
Master network that
107
Corrective Actions
Go to Menu L- Configure I/O and
change the Air Flow Switch
action setting
Check pump
Check electrical wiring
Replace flow Switch
Go to Menu L- Configure I/O and
change the Water Flow Switch
action setting
Allow water or moisture to dry
and alarm will auto reset
Check for 10K resistance,
replace sensor if necessary
Check 24 volts at the Water
Detection Module
Go To I/O Input in Menu L Floor
Water Switch and change the
Action
Check optional alarm settings
and inputs
Check BMS
Check zone master settings and
humidity set points of all units.
Check optional alarm settings
and inputs
Check BMS