MENU C – CLOCK/SCHEDULER
Day: The day of the week is for display only and is based on the date setting.
Date: Setting for the current date (in Month/Day/Year format).
Time: Setting for the current time (in 24 hour format).
Important Notice: Set-Back should only be enabled for non-critical
applications where the unit may be turned off or the set points be offset
without any damage to sensitive electronic equipment. A typical
application for the scheduler is in a comfort cooling application.
Set-Back Enable: Enables the scheduler features. Note: if the scheduler is set to
enabled, you must continue to setup the weekday schedule or the unit will not be
able to turn on.
Override Schedule: Temporarily overrides the set-back scheduler (daily, holiday
or special day) for a period of the Override Time.
Override Time: The time that an override will last. The range of adjustment is 1 to
12 hours with a default value of 4 hours.
22
Need help?
Do you have a question about the dap4 and is the answer not in the manual?