Alarm Screen
Description &
Classification
Compressor
Compressor
Short Cycle
has started
more than 10
times in an
hour.
** Urgent
Possible Causes
Excessive Airflow
across the evaporator
coil
Heavy Load
Return duct damaged
Sensing Bulb is loose
Over charge of
refrigerant
Non-condensable
Undersized refrigerant
pipe
Expansion valve
Overfeed
Faulty high pressure
switch. Cut out:
R410A at 575 PSI or
R407 at 450PSI.
Incorrect settings on
the controller
Not enough Heat Load
or Oversized System
Temperature Dead
Band is set too low
Humidity Dead Band
is too low (causing
frequent dehum
cycles).
103
Corrective Actions
High indoor temperature, check
blower speed, and check
equipment selection
Check return duct for leakage
and check temperature entering
evaporator coil
Tighten bulb bracket
Check sub-cooling (8-10) and
adjust charge if necessary
Recover charge, evacuate, then
re-charge system
Refer to your respective IOM
manuals for more details. Follow
the recommended tables.
Adjust and check valve
operations
Replace high pressure switch
Go to Menu L- Configure I/O and
change the High Pressure Switch
action setting
Check for heat load
Check and raise Temperature
Dead Band
Check and raise Humidity Dead
Band