MENU C – Clock/Scheduler continued
Note: The Special Day scheduler will override the Weekday scheduler on the date
that the Special Day scheduler is active.
Setting: This is the action that should occur at the selected start date. This action
will remain in effect until the next start date that is set to have an action. The
default value is to take No Action. There are four possible action settings:
No Action (--------): The scheduler will continue running the last action
taken either this day or the previous day.
Normal SP : Use the normal temperature and humidity settings. This action
will also turn the unit on if it was currently off.
Set-Back: Apply the setback offsets to the normal temperature and
humidity settings. This action will also turn the unit on if it was currently off.
Turn Off: The unit will be turned off until the timed action of Normal SP or
Set-Back is executed. When the unit is off due to the scheduler, the main
status screen will indicate the unit status as OFFbySCH. Caution: The Turn
Off action must be followed by the Normal SP or a Set-Back action for the
unit to turn back on.