MENU J – FACTORY SETTINGS (factory level) continued
Note: The Fan Air Flow screen is only displayed when CW or DX fan mode is set
to modulate to maintain Air Flow.
Number of Fans: The total number of fans on this unit. Range of adjustment is
from one to four fans, with a default of three fans.
Fan K-Factor: This setting should correspond to the K-Factor specified by the
manufacturer of the fan.
Minimum Airflow: The lowest airflow setting that the fans should produce. Range
of adjustment is 0 to 32000cfm with a default setting of 2000cfm.
Maximum Airflow: The highest airflow setting that the fans should produce.
Range of adjustment is 0 to 32000cfm with a default setting of 32000cfm.
Set Point: The airflow setting that the fans will be modulated to maintain. Range of
adjustment is between the fan minimum and maximum settings.
39