MENU K – ALARMS & LIMITS (Service Level) continued
No Water Flow Action: This is the setting of what should happen in the event that
no water flow is detected (flow sensor required). The water flow alarm cannot be
disabled and is checked only when there is a cooling demand and the CW valve
has opened at least 60%. The selections for the alarm action are:
Alarm Only: (Default) The alarm will not cause any change in operation.
Turn Compressors Off: The compressors will be shut down and kept off
for 5 minutes after the water flow alarm is no longer active. A countdown
showing the time remaining until the compressors will be allowed to run is
shown on the no water flow alarm screen.
Wtr Flow Alm Dly: This is the amount of time that the water flow alarm is
delayed from occurring. The selection is from 5 to 180 seconds with a
default of 5 seconds.
No Air Flow: The air flow alarm cannot be disabled and is checked when the fan
is on. The alarm is delayed for about a minute when the system is initially turned
on.
Air Flow Alm Dly: This is the amount of time that the air flow alarm is
delayed from occurring. The selection is from 5 to 180 seconds with a
default of 5 seconds.