MENU K – ALARMS & LIMITS (Service Level) continued
Comp Short Cycle: When set to "Yes" (default) the short cycle alarm is enabled
and will occur when a short cycle condition is detected.
Notice: A short cycle condition will occur regardless of whether the short cycle
alarm is enabled of not. It is caused when any compressor cycles on and off more
than 10 times per hour. An additional 60 seconds is added to the minimum off time
setting of the compressor as result of a short cycle condition.
Floor Water Alarm Action: This is the setting of what should happen in the event
that floor water is detected. The floor water alarm cannot be disabled. The
selections for the alarm action are:
Alarm Only: (Default) The alarm will not cause any change in operation.
Lockout Comps: The compressors will be shut down and kept off until the
floor water alarm is no longer active.
Shutdown Unit: The unit will be shut down and kept off until the floor water
alarm is no longer active.
Reset Alarm Log: Selecting "Yes" will cause the alarm log in the Historical Data
menu to be reset.
Alarm Screen Contact: This selection is for the information that will be displayed
at the bottom of all alarm screens. Selections are: No Contact Message (default),
Data Proc Mngr, Maint Engineer, Service Company and Custom Message.
When the custom message is selected, the bottom line allows you to set each
individual character of the message. The message may contain up to 22
characters. Selection of each character is letters A to Z (all upper case) and
numbers 1 to 9 and also space and punctuation marks.