VistaKey Installation Guide
↓ Access Point Number
01 PREALARM TIME
5s
↓ Access Point Number
01 RELATCH on
timeout/closed
5–16
DOOR OPEN TIME
(3 Seconds)
Acceptable 1-digit entries are as follows:
0 = 10 sec.
4 = 2 min.
1 = 20 sec.
5 = 5 min.
2 = 30 sec.
6 = 10 min.
3 = 1 min.
7 = 30 min.
Press [ ] to accept the entry.
The pre-alarm time is used to warn a person holding the access door
open that a zone fault (resulting in an alarm when enabled) will
0
occur if the door is not closed before the alarm timeout expires. (For
example, as shown in the above figure, if the alarm timeout is set
for 10 seconds and the pre-alarm time is 5 seconds, the pre-alarm
warning commences 5 seconds before the alarm condition [zone
fault] is reported to the VISTA panel.) The pre-alarm signal is
output from the VistaKey on the Trigger output and if used, must
be enabled when responding to the PREALARM TRIG prompt later
in this section.
Enter 1 digit for the door pre-alarm timeout value. Acceptable 1-
digit entries are as follows:
0 = 5 sec.
4 = 1 min.
1 = 10 sec.
5 = 2 min.
2 = 15 sec.
6 = 5 min.
3 = 30 sec.
7 = 10 min.
Press [ ] to accept the entry.
When a DSM zone is installed at the door, the system can determine
that the door has closed before the amount of time that it was to
0
remain unlatched (see "Door Opn Time" prompt above). When the
"relatch on timeout/closed" option is selected, the system
automatically relatches the door when it closes or at timeout,
whichever occurs first. The "timeout/closed" option prevents a late-
comer from pushing an unlatched door open. When "relatch on
open" is selected, the door strike or mag lock will relatch as soon as
the door is opened.
Press 0 (relatch on timeout or door closing, whichever occurs first)
or 1 (relatch on door opening).
Press [ ] to accept the entry.
ALARM TIMEOUT
(10 Seconds)
PREALARM TIME
(5 Seconds)
3 + 10 = 13 Seconds)
DOOR PROPPED
EVENT IS LOGGED
AND ALARM
OCCURS (WHEN
(ENABLED) AT 13
SECONDS IF
DOOR IS STILL
OPEN