Initial System Test - ADEMCO VistaKey-SK Installation & Setup Manual

Single-door access control starter kit
Hide thumbs Also See for VistaKey-SK:
Table of Contents

Advertisement

VistaKey Installation Guide

Initial System Test

ACS access grants and egress grants are alarm type events in the alarm panel log. If you have
changed the default values for "Event Log Types" (alarm panel field 1*70) so that alarm type
events are not logged, the following procedure can not be used. To use this procedure, refer to
the "Data Field Program Mode" descriptions in your alarm panel installation and setup guide and
temporarily enable alarm type events in field 1*70 to perform this test.
The operation of the VistaKey should be checked to verify that the installed hardware is
functional. To perform an initial test of the VistaKey, perform the following procedure.
1. Using any of the alarm panel keypads, enter Installer Code + # + 78. The keypad
displays:
2. Press 2 on the keypad. The keypad displays:
3. Press [ ] on the keypad. The keypad starts beeping at a periodic rated indicating the
system is in the test mode and the keypad displays:
4. Swipe any ADEMCO proximity card past the card reader. If the unit is properly installed,
the mag lock or door strike will activate, and the green LED will temporarily illuminate
on the card reader. If the test is successful, advance to step 5. If the mag lock or door
strike does not activate, and the green LED does not illuminate, do the following:
a. Exit the ACS TEST MODE by entering Installer Code + # + 78 + 0 + *. The keypad
stops beeping and displays:
b. Check all wiring to the units and that external power is applied.
c. Return to Step 1 to repeat the test.
5. If additional VistaKeys have been installed for additional access points, repeat step 4 at
the card reader for each of the additional access points.
6. Exit the ACS Test Mode by entering Installer Code + # + 78 + 0 + * at the keypad. The
keypad stops beeping and displays:
7. Use the following procedure to verify that all access points tested are logged in the alarm
panel's event log.
a. Using any of the alarm panel keypads, enter Installer Code + # + 60 to view the
alarm control panel log. The keypad displays:
b. Press 1 on the keypad. The keypad displays:
4–8
ACS TEST MODE
0 = quit
0
ACS TEST MODE
GRANT ALL CARDS
2
GRANT ALL CARDS
ACS TEST MODE
****DISARMED****
READY TO ARM
****DISARMED****
READY TO ARM
ENTER 0= RECENT
1=COMPLETE DUMP
SCAN LOG BY PART
0=NO
1-8=PART #