Summary Of Connections - ADEMCO VistaKey-SK Installation & Setup Manual

Single-door access control starter kit
Hide thumbs Also See for VistaKey-SK:
Table of Contents

Advertisement

THIS DEVICE COMPLIES WITH PART 15 CLASS A
LIMITS OF FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS:
(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
(2) IT MUST ACCEPT ANY INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
CONNECT
TRANSFORMER
TO
24 HOUR
OUTLET
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARDS 70 &
74 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA. 02269).
PRINTED INFORMATION DESCRIBING PROPER
MAINTENANCE, EVACUATION PLANNING AND
INPUT POWER: 12-24VDC,
REPAIR SERVICE IS TO BE PROVIDED WITH
250MA MAX.
THIS EQUIPMENT.
INPUT POWER SUPPLY
MUST BE POWER LIMITED
AND CONNECTED TO A
24-HR. OUTLET.
FOR ADDITIONAL RATINGS AND
SPECIFICATIONS, REFER TO
INSTALLATION INSTRUCTION
K4005.
WEEKLY TESTING IS REQUIRED
TO ENSURE PROPER OPERATION
OF THIS SYSTEM.
THESE ITEMS ARE OPTIONAL
AND ARE INCLUDED IN THE
OPTIONAL
VISTAKEY-SK OR MAY BE
PURCHASED SEPARATELY.
12V
7 AHR
BAT
OPTIONAL †
N8167
18 VAC
50VA
1
2 3 4 5 6 7 8 9 10
11 12
TB 1
K1
DOOR
CONTROL
RELAY
1
2
3
4
TB 3
5
6
7
8
+
VISTAKEY
OPTIONAL †
POWER SUPPLY
+
1
2 3 4 5 6 7 8 9 10
+
+
+
+
+
+
+
-
+
14V MAX (12V @ 85-160mA Nominal)
GND
POLLING LOOP +
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP -
POLLING LOOP TERMINALS.
GND
ZONE A (DSM)
ZONE B (RTE)
ZONE C (General)
GND
POLE Door Strike/Mag Coil
N/C MAG COIL POWER
+12VDC
TO ONLY ONE OF
N/O DOOR STRIKE POWER
THESE INPUTS.
(SEE NOTE 6)
RELAY CONTACT RATINGS:
3A @ 28VDC MAX. (RESISTIVE LOAD)
RDR LED
GND
DATA 1
DATA 0
GND (NOTE 3)
CONNECT ONLY
+5V
ONE OF THESE
+12V
TO READER
TRIGGER (SEE NOTE 4)
ADDRESS SELECT SWITCH

SUMMARY OF CONNECTIONS

RED HEARTBEAT LED
YELLOW BATT SUPERVISION LED
GREEN AC SUPERVISION LED
+
+
+
WARNING: POWER SUPPLY TERMINAL 3 IS COMMON
TO THE POWER SUPPLY GROUND PLANE AND
MUST NOT BE CONNECTED.
FAILURE TO HEED THIS WARNING MAY CAUSE A
GROUND FAULT IN THE VISTA FIRE/BURGULARY SYSTEM.
SEE
NOTE 5
OPTIONAL †
NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.
NOTE 2: BEFORE INSTALLING THE SUPPLIED TRANSIENT
PROXIMITY
SUPPRESSION DEVICE,CHECK DOOR/STRIKE MAG LOCK DIRECTIONS.
READER
5365BGP
NOTE 3: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BE USED
INSTEAD OF TB3 TERMINAL 2. TB3 TERMINAL 2 AND 5 ARE A COMMON
GROUND.
NOTE 4: WHEN USING TRIGGER TO TURN ON A LED OR BUZZER,
RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7. TRIGGER
READER INTERFACE CABLE
RATING 15 mA @ 12VDC.
NOTE 5: WHEN MOUNTING POWER SUPPLY IN CABINET, USE NYLON
WASHER ON SCREW INSERTED AT THIS LOCATION.
NOTE 6: WHEN INSTALLING A VISTAKEY-SK, OBTAIN +12VDC BY
CONNECTING TERMINAL 11 OR 12 TO TB1 TERMINAL 1.
SEE NOTE 2
_
+