Figure 3-1: Vistakey Wiring - ADEMCO VistaKey-SK Installation & Setup Manual

Single-door access control starter kit
Hide thumbs Also See for VistaKey-SK:
Table of Contents

Advertisement

VistaKey Installation Guide
indicates a card not linked to a user. If the card was linked to a user, the user number
would be displayed.
If an access point shows up incorrectly (e.g., you tested access points (VistaKey
addresses) 1 and 2 but the log shows the zone for access point 1 twice), check the
address switch setting in the VistaKey for the access point that is missing. If an access
point test is missing entirely, recheck the system wiring.
g. Press [ ] on the keypad to exit the Log View Mode.
The quick installation is complete and the access point(s) are ready to be programmed into
the alarm panel control using the procedures provided in Section 5: Programming.
CONNECT TO
24 HOUR OUTLET
OPTIONAL
12V
TRANSFORMER
7 AHR
N8167
BAT
18 VAC
50VA
1
2 3 4 5 6 7 8 9 10
11 12
TB 1
K1
DOOR
CONTROL
RELAY
1
2
3
4
TB 3
5
6
7
8
+
VISTAKEY
NOTES:
• Local Power and door strike/mag lock power must be supplied from the VistaKey-SK for UL installations.
• Observe the color coding of your reader if not using the ADEMCO reader.
• The use an optional battery on the power supply has not been approved for UL installations.
3–4
POWER SUPPLY
+
1
2 3 4 5 6 7 8 9 10
+
+
+
-
14V MAX
GND
POLLING LOOP +
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP -
POLLING LOOP TERMINALS.
GND
ZONE A (DSM)
ZONE B (RTE)
ZONE C (General)
GND
POLE Door Strike/Mag Coil
N/C MAG COIL POWER
+ 12 VDC TO ONLY
ONE OF THESE INPUTS.
N/O DOOR STRIKE POWER
(FROM TB1-1)
RELAY CONTACT RATINGS:
3A @ 28VDC MAX. (RESISTIVE LOAD)
RDR LED
(ORANGE)
GND
(BLACK)
DATA 1
(WHITE)
DATA 0
(GREEN)
GND
NO
+5V
CONNECTION
+12V
(RED)
TRIGGER
ADDRESS SELECT
SWITCH POSITIONS:
1-9 = ACCESS POINT 1-9
A = ACCESS POINT 10
B = ACCESS POINT 11
C = ACCESS POINT 12
D = ACCESS POINT 13
E = ACCESS POINT 14
F = ACCESS POINT 15

Figure 3-1: VistaKey Wiring

+
+
+
+
+
+
+
+
SUPPLIED TRANSIENT SUPPRESSION DEVICE.
BEFORE INSTALLING,CHECK DOOR/STRIKE
MAG LOCK DIRECTIONS.
PROXIMITY
READER
5365BGP
READER INTERFACE CABLE
WARNING: POWER SUPPLY TERMINAL 3 IS COMMON
TO THE POWER SUPPLY GROUND PLANE AND
MUST NOT BE CONNECTED.
FAILURE TO HEED THIS WARNING MAY CAUSE A
GROUND FAULT IN THE VISTA FIRE/BURGULARY SYSTEM.