FX-2200 Programming Manual
There is a special Level 2 passcode that is variable from day to day. It can be obtained from
Mircom if the Level 2 passcode is forgotten.
Memory
This function is restricted to Privilege Level 2. This menu has the following options:
46
Erase Configuration: This erases all initiating circuit, bell, relay, and privilege values
entered from the keypad and LCD menu, and replace them with default values. With FX2
programs, this has no effect on information contained in the downloaded database.
Confirmation is asked before erasure. After the Configuration has been erased, the panel
must be reset using the reset button at the top of the Main Circuit Board, if the panel does
not do this automatically. The following items are not erased: Serial Number, Clock
Calibration, Level 1 Passcode, Level 2 Passcode, Main Board Type, Input Circuit
Modules.