FX-2200 Programming Manual
Groups
Groups is a comma separated list of all the groups that the point is to use for relates. Up to ten
groups can be listed. These groups are assigned to the point itself and does not change as the
current output panel changes. Relates that are part of the groups are not shown in the Relate
Window but can be shown on the Map Window if so desired.
Panel List
The Panel List is a list-box located in the top left corner of the window. It lists all the panels, both
Control and Annunciator, that are defined in the system along with their panel message. The high-
lighted entry in the list is the one that is being related to by the current input. When a different
panel is selected, all the controls in the window change to reflect this. Use the <Backspace> key
in order to quickly re-position the current selection to another panel.
Outputs List
The Outputs List shows the programmable outputs of the panel. It is not shown for annunciators. It
lists all outputs, along with their definition and current state. The states are *on* for selected, blank
for not selected, act if they activated by default, and n/a for not available. A blank definition is for
unused outputs. Bell and Strobe outputs can only be selected for Fire Alarm type inputs. If
Complex Releasers are enabled, releasers can have three other states: Fast which operates the
releaser immediately regardless of any delay that is programmed in; *A* or *B* which allow for
AND logic. The releaser will not operate until both an A and a B input have been activated. Use the
<space> key or double click on the entry to cycle between available selections. Use the
<Backspace> key in order to quickly reposition the current selection to another output.
Relays List
The Relays List shows the general purpose function relays of the panel. It is not shown for
annunciators. Each is listed by number and state. The states are *on* for selected, n/a for not
available, and blank for not selected. Use the <space> key or double click on the entry to cycle
between available selections. Use the <Backspace> key in order to quickly re-position the current
selection to another relay.
LEDs List
The LEDs List shows the LED zones available on the panel or annunciator. This is not shown if the
panel has no LEDs. Each is listed by number and state. The states are *on* for selected, blank for
not selected and n/a for not available. Use the <space> key or double click on the entry to cycle
between available selections. Use the <Backspace> key in order to quickly re-position the current
selection to another LED. The actual number of LED zones varies depending upon the panel or
annunciator.
Device List
The Device List shows the addressable devices that can be related to the current point. For
system inputs and groups, it is displayed only if there are any control modules defined for the
panel; for switches, it is displayed if there are any addressable detectors or control modules
defined. Each entry shows the devices's address (panel.circuit.device), its state and its device
message. The states are *on* for selected and blank for not selected. Devices that are not
available are not shown. Use the <space> key or double click on the entry to cycle between
available selections.
Evac
THe EVAC checkbox is an option for fire alarm type inputs only. Checking this option will cause all
bells and strobes to operate in second stage (evacuation) mode.
38