entering any number to view the first detector in the database. Each detector is
displayed in turn, showing the current sensitivity and allowing for it to be changed or the
next detector to be displayed. Press <Clear> to stop viewing the detector list.
-- PRINT: Print a list of all detectors that have a sensitivity other than the one selected in
the database. This option is not shown if no manual sensitivities have been set.
-- ALL DEFAULT: Change all manual sensitivity settings to the default values set in the
database.
Bypass: This function can be set to Privilege Level 1 or 2. This selects devices to be
bypassed. A bypassed device is ignored by the system. Addressable bypasses are
retained when the panel is re-booted. Only devices included in the database can be
bypassed. Bypasses are annunciated by a common trouble condition. The Bypass menu
has the following options:
-- ON: Select devices to be bypassed. Enter the circuit and device number. Press
<Enter> to accept the device and to enter the next one. Pressing <Clear> removes
any numbers entered. Pressing either <Enter> or <Clear> with no numbers
displayed ends the input mode.
-- OFF: Select bypassed devices to be returned to normal operation. Each bypassed
device is listed in order. Select next to keep the bypass on or select OFF to remove the
bypass. After the last device, display returns to the Bypass menu. Press <Clear> to
return to the Bypass Menu. This option is not available if there are no devices
bypassed.
-- ALL OFF: Remove all bypasses, if any, from the system. The number of bypassed
devices is displayed next to this option.
Test: Select devices to be tested. Test Mode must be active for this selection to be
available. All devices selected for testing are automatically deselected when Test Mode is
turned off. The Test Menu has the following options:
-- ON: Select devices for testing. Enter the circuit and device number, or enter the circuit
number only to select all devices on the circuit. Press <Enter> to accept the device
and to enter the next one. Pressing <Clear> removes any numbers entered. Pressing
either <Enter> or <Clear> with no numbers displayed ends the input mode.
-- OFF: Select devices under test to be returned to normal operation. Each device under
test is listed in order. Select next to keep the device under test or select OFF to remove
the test mode. After the last device, display returns to the Test menu. Press <Clear> to
return to the Test Menu. This option is not available if there are no devices selected for
testing.
-- ALL OFF: Remove all devices being tested, if any, from the test mode. The number of
devices being tested is displayed next to this option.
Control Modules: This function can be set to Privilege Level 1 or 2. Allow for the manual
operation of the control modules included in the database. There are three states
available: Automatic (controlled by device inputs), Manual On, and Manual Off. This mode
is retained if the panel is re-booted. Manually controlled modules are annunciated by a
common trouble condition. The menu has the following options:
-- SELECT: Change the Auto/On/Off state of control modules. The first screen asks for a
circuit and device number. Enter the circuit and device or press <Enter> without
entering any number to view the first control module in the database. Each control
module is displayed in turn, showing the current state and allowing for it to be changed
or the next control module to be displayed. Press <Clear> to stop viewing the control
module list.
-- ALL AUTO: Change any control modules that are forced on or off back to automatic
mode.