AX Security Control Panel User Manual
The panel is in "AP" mode. Solution: switch the panel to "station" mode, and then
try to enter the RF signal query mode again.
A.3 Zone Fault
A.3.1 Zone is Offline
Fault Description:
View status of zones which displays offline.
Solution:
Check whether the detector reports undervoltage. Replace the detector battery
A.3.2 Zone Tamper-proof
Fault Description:
View status of zones which displays tamper-proof.
Solution:
Recovery detector tamper-proof button.
A.3.3 Zone Triggered/Fault
Fault Description:
View status of zones which displays triggered/fault.
Solution:
Reset the detector.
A.4 Problems While Arming
A.4.1 Failure in Arming (When the Arming Process is Not Started)
Fault Description:
When the panel is arming, prompt arming fails.
Solution: