Define the actual value source by clicking in the appropriate field
A window with the relevant parameters opens
Select analog input 1 which is saved in r755[1] and click OK
Set the smoothing time for the actual value (P2265) by clicking the appropriate field
7
Enter 10s
8
Define ramp-up/ramp-down time by clicking in the appropriate field
A window opens
Enter 30 s for both values and close the window
3
5
6
7
8
9
10
The ramp up and ramp down times
set during basic commissioning do
not apply to the PID controls. It is
important that the ramp-up and
ramp-down times and smoothing
times are set in the PID window.
NOTE