Siemens Sinamics G120P Instruction Manual page 58

Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Motor Cos Phi
• Enter the correct motor cos phi according to the motor rating plate
Rated motor speed
• Enter the appropriate rated motor speed (please see the motor rating plate on page 34)
• In our example: "1350 rpm"
• Turn the wheel to select the appropriate numbers
• Press OK to confirm the number
Current limit
• The drive suggests a current limit with factor 1.5 of the rated motor current.
Activating motor data identification
• Motor identification is recommended for verification and optimization of all motor data
• If it is safe choose motor "data identification at standstill"
• Motor data identification will be performed when the motor is switched on
• Press OK to confirm
Operator Panels BOP-2 and IOP-2:
46
0.75
OK
OK
1350 rpm
OK
Adjust this value if needed.
x 1.5
OK
OK
ID standstill
OK
Intelligent Operator Panel
OK
OK