Response
The register data in the response message are packed as 2
bytes per register, with the binary contents right justified
within each byte. For each register, the first byte contains
the high-order bits and the second contains the low-order
bits.
Example: Hex 0016E360 = 1.500.000 = 1,500 RPM.
Field Name
Example (HEX)
Slave Address
01
Function
03
Byte Count
04
Data HI
00
(Register 3030)
Data LO
16
(Register 3030)
Data HI
E3
(Register 3031)
Data LO
60
(Register 3031)
Error Check
-
(CRC)
Table 7.26 Response

7.10.5 Preset Single Register (06 HEX)

Description
This function presets a value into a single holding register.
Query
The query message specifies the register reference to be
preset. Register addresses start at zero, that is, register 1 is
addressed as 0.
Example: Write to 1–00 Configuration Mode, register 1000.
Field Name
Example (HEX)
Slave Address
01
Function
06
Register Address HI
03 (Register address 999)
Register Address LO
E7 (Register address 999)
Preset Data HI
00
Preset Data LO
01
Error Check (CRC)
-
Table 7.27 Query
Response
The normal response is an echo of the query, returned
after the register contents have been passed.
®
VLT
AQUA Drive FC 202 Design Guide
Field Name
Slave Address
Function
Register Address HI
Register Address LO
Preset Data HI
Preset Data LO
Error Check (CRC)
Table 7.28 Response

7.11 Danfoss FC Control Profile

7.11.1 Control Word According to FC
Bit
no.:
Illustration 7.16 CW Master to Slave
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Explanation of the Control Bits
Bits 00/01
Bits 00 and 01 are used to choose between the four
reference values, which are pre-programmed in 3-10 Preset
Reference according to Table 7.31.
®
MG20Z102 - VLT
is a registered Danfoss trademark
Example (HEX)
01
06
03
E7
00
01
-
Profile (8-10 Control Profile=FC
profile)
Master-slave
CTW
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit value=0
Bit value=1
Reference value
external selection lsb
Reference value
external selection msb
DC brake
Ramp
Coasting
No coasting
Quick stop
Ramp
Hold output frequency
use ramp
Ramp stop
Start
No function
Reset
No function
Jog
Ramp 1
Ramp 2
Data invalid
Data valid
No function
Relay 01 active
No function
Relay 02 active
Parameter set-up
selection lsb
Parameter set-up
selection msb
No function
Reverse
7
Speed ref.
179
7