Modbus telegram. Coil 127 decimal is addressed as coil
007Ehex (126 decimal).
Holding register 40001 is addressed as register 0000 in the
data address field of the telegram. The function code field
already specifies a holding register operation. Therefore,
the 4XXXX reference is implicit. Holding register 40108 is
addressed as register 006Bhex (107 decimal).
Coil
Description
number
1–16
Frequency converter control word
(see Table 7.16).
17–32
Frequency converter speed or
setpoint reference range 0x0–
0xFFFF (-200% ... ~200%).
33–48
Frequency converter status word
(see Table 7.17).
49–64
Open-loop mode: Frequency
converter output frequency.
Closed-loop mode: Frequency
converter feedback signal.
Parameter write control (master to
slave).
0 = Parameter changes are written
to the RAM of the frequency
65
converter.
1 = Parameter changes are written
to the RAM and EEPROM of the
frequency converter.
66–65536 Reserved.
Table 7.15 Coil Register
Coil
0
01
Preset reference lsb
02
Preset reference msb
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze frequency
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up lsb
15
16
No reversing
Table 7.16 Frequency Converter Control Word (FC Profile)
MG18N202
Design Guide
Signal
direction
Master to slave
Master to slave
Slave to master
Slave to master
Master to slave
1
No DC brake
No coast stop
No quick stop
No freeze frequency
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
Danfoss A/S © 12/2015 All rights reserved.
Coil
0
33
Control not ready
34
Frequency converter not
ready
35
Coast stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of frequency range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Table 7.17 Frequency Converter Status Word (FC Profile)
1
Control ready
Frequency converter ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning
59