8.3 Acoustic Noise or Vibration

If the compressor or the equipment driven by the
compressor - for example, a fan - is making noise or
vibrations at certain frequencies, configure the following
parameters or parameter groups to reduce or eliminate the
noise or vibrations:
Parameter group 4-6* Speed Bypass.
Set parameter 14-03 Overmodulation to [0] Off.
Switching pattern and switching frequency
parameter group 14-0* Inverter Switching.
Parameter 1-64 Resonance Dampening.
The acoustic noise from the frequency converter comes
from 3 sources:
DC intermediate circuit coils
Integral fan
RFI filter choke
8
8
Enclosure
H3
H4
H5
Table 8.3 Typical Values Measured at a Distance of 1 m
from the Unit
74
®
VLT
Compressor Drive CDS 803
Level [dBA]
53.8
64
63.7