How to Program
Parameter
Parameter 8-01 Control Site
Parameter 8-30 Protocol
Parameter 8-32 Baud Rate
Parameter 20-00 Feedback 1 Source
Parameter 20-01 Feedback 1
Conversion
Table 6.6 Closed-loop Applications Set-up
Changes made
Changes Made lists all parameters changed from default
settings.
The list shows only parameters which have been
changed in the current edit set-up.
Parameters which have been reset to default
values are not listed.
The message Empty indicates that no parameters
have been changed.
To change parameter settings
1.
To enter the Quick Menu, press [Menu] until
indicator in display is placed above Quick Menu.
2.
Press [
] [
] to select quick guide, closed-loop
set-up, compressor set-up, or changes made, then
press [OK].
3.
Press [
] [
] to browse through the parameters in
the Quick Menu.
4.
Press [OK] to select a parameter.
5.
Press [
] [
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter Status, or press
[Menu] once to enter Main Menu.
MG18N202
Design Guide
Option
[0] Digital and ctrl.word
[1] Digital only
[2] Controlword only
[0] FC
[2] Modbus RTU
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
[0] No function
[1] Analog Input 53
[2] Analog Input 54
[3] Pulse input 29
[100] Bus Feedback 1
[101] Bus Feedback 2
[0] Linear
[1] Square root
Danfoss A/S © 12/2015 All rights reserved.
Default
Function
[0] Digital and
Select if digital, bus, or a combination of both
ctrl.word
should control the frequency converter.
[0] FC
Select the protocol for the integrated RS485
port.
[2] 9600 Baud
Select the baud rate for the RS485 port.
[0] No function
Select which input to use as the source of the
feedback signal.
[0] Linear
Select how to calculate the feedback.
The Main Menu accesses all parameters
1.
Press [Menu] until indicator in display is placed
above Main Menu.
2.
Press [
] [
] to browse through the parameter
groups.
3.
Press [OK] to select a parameter group.
4.
Press [
] [
] to browse through the parameters in
the specific group.
5.
Press [OK] to select the parameter.
6.
Press [
] [
] to set/change the parameter value.

6.3.3 Main Menu

Press [Main Menu] to access and program all parameters.
The main menu parameters can be accessed readily unless
a password has been created via parameter 0-60 Main
Menu Password.
For most applications, it is not necessary to access the
main menu parameters. The quick menu provides the
simplest and quickest access to the typical required
parameters.
6
6
47