7.4.6 The Data Field

The structure of data blocks depends on the type of telegram. There are 3 telegram types, and the type applies for both
control telegrams (master⇒slave) and response telegrams (slave⇒master).
The 3 types of telegram are:
Process block (PCD)
Parameter block
Text block
Process block (PCD)
The PCD is made up of a data block of 4 bytes (2 words) and contains:
Control word and reference value (from master to slave).
Status word and present output frequency (from slave to master).
STX
LGE
ADR
Illustration 7.6 Process Block
Parameter block
The parameter block is used to transfer parameters between master and slave. The data block is made up of 12 bytes (6
words) and also contains the process block.
STX
LGE
ADR
Illustration 7.7 Parameter Block
Text block
The text block is used to read or write texts via the data block.
STX
LGE
ADR
PKE
Illustration 7.8 Text Block
MG18N202
Design Guide
PCD1
PWE
PKE
IND
high
IND
Ch1
Ch2
Danfoss A/S © 12/2015 All rights reserved.
PCD2
PWE
PCD1
low
Chn
PCD1
BCC
PCD2
BCC
PCD2
BCC