Si37-701
L4
3.36 "
" Outdoor Unit:
Temperature Rise
L4
Remote
Controller
Display
Applicable
REYQ8P~48P
Models
Method of
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Detection
Malfunction
When the temperature of the inverter radiation fin increases above 87°C.
Decision
Conditions
Supposed
Causes
Troubleshooting
Malfunction of Inverter Radiating Fin
Actuation of fin thermal (Actuates above 87°C)
Defect of inverter PC board
Defect of fin thermistor
Troubleshooting by Indication on the Remote Controller