Bs Units - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Si37-701
1.3

BS Units

Model
Power Supply
Total Capacity Index of Indoor Unit
No. of Connectable Indoor Units
Casing
Dimensions: (H×W×D)
Sound Absorbing Thermal Insulation
Material
Liquid Pipes
Indoor
Unit
Gas Pipes
Piping
Liquid Pipes
Connection
Outdoor
Suction Gas Pipes
Unit
HP/LP Gas Pipes
Weight
Standard Accessories
Drawing No.
Note:
1 When connecting with a 20 to 50 class indoor unit, connect to the attached pipe to the field pipe.
2 When connecting with an indoor unit of 150 or more and 160 or less, connect to the attached pipe to the field pipe.
3 When connecting with a 200 class, or more than 160 and less than 200 class indoor unit, connect to the attached pipe to the field pipe.
Connection Range for BS Unit
Components
Indoor unit total capacity
Note:
Specifications
BSVQ100PV1
1 Phase 50Hz 200-240V
20 to 100
Max. 5
Galvanized steel plate
mm
207×388×326
Foamed polyurethane, Flame resistant
needle felt
9.5mm C1220T (brazing connection)
15.9mm C1220T (brazing connection)
9.5mm C1220T (brazing connection)
15.9mm C1220T (brazing connection)
12.7mm C1220T (brazing connection)
kg
14
Installation manual, Attached pipe
Insulation pipe cover, Clamps
C: 4D057926
(Braze the connection between the attached and field pipe.)
(Braze the connection between the attached and field pipe.)
(Braze the connection between the attached and field pipe.)
Outdoor unit
model name
REYQ8P
REYQ10P
REYQ12P
REYQ14P
REYQ16P
REYQ18P
REYQ20P
REYQ22P
REYQ24P
REYQ26P
REYQ28P
REYQ30P
REYQ32P
REYQ34P
REYQ36P
REYQ38P
REYQ40P
REYQ42P
REYQ44P
REYQ46P
REYQ48P
Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% from single outdoor units, 160% from
double outdoor units, 130% from triple outdoor units.
BSVQ160PV1
1 Phase 50Hz 200-240V
More than 100 but 160 or less
Max. 8
Galvanized steel plate
207×388×326
Foamed polyurethane, Flame resistant
needle felt
1
9.5mm C1220T (brazing connection)
1
15.9mm C1220T (brazing connection)
9.5mm C1220T (brazing connection)
15.9mm C1220T (brazing connection)
12.7mm C1220T (brazing connection)
14
Installation manual, Attached pipe
Insulation pipe cover, Clamps
C: 4D057927
Total capacity of connectable indoor
units
100 to 260 (400)
125 to 325 (500)
150 to 390 (600)
175 to 455 (700)
200 to 520 (800)
225 to 585 (720)
250 to 650 (800)
275 to 715 (880)
300 to 780 (960)
325 to 845 (1,040)
350 to 910 (1,120)
375 to 975 (1,200)
400 to 1,040 (1,280)
425 to 1,105 (1,105)
450 to 1,170 (1,170)
475 to 1,235 (1,235)
500 to 1,300 (1,300)
525 to 1,365 (1,365)
550 to 1,430 (1,430)
575 to 1,495 (1,495)
600 to 1,560 (1,560)
Specifications
BSVQ250PV1
1 Phase 50Hz 200-240V
More than 160 but 250 or less
Max. 5
Galvanized steel plate
207×388×326
Foamed polyurethane, Flame resistant
needle felt
9.5mm C1220T (brazing connection)
2
22.2mm C1220T (brazing connection)
9.5mm C1220T (brazing connection)
2
22.2mm C1220T (brazing connection)
2
19.1mm C1220T (brazing connection)
15
Installation manual, Attached pipe
Insulation pipe cover, Clamps
C: 4D057928
Number of connectable
indoor units
13 (20)
16 (25)
19 (30)
22 (35)
26 (40)
29 (36)
32 (40)
35 (44)
39 (48)
42 (52)
Same number of
45 (56)

BS units

48 (60)
52 (64)
55 (55)
58 (58)
61 (61)
64 (64)
3
3
3
47