Other Control

5.

Other Control

5.1

Backup Operation

If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor
unit from operating, and then conduct emergency operation only with operational compressors
or outdoor units.
"Emergency operation with remote controller reset" and "Emergency operation with outdoor unit
PC board setting" are available
Applicable model
(1) Emergency operation with remote controller reset
[Operating method]
[Details of operation]
(2) Emergency operation with outdoor unit PC board setting
[Setting method]
[Details of operation]
5.2

Demand Operation

In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using "Demand 1 Setting" or "Demand 2 Setting".
To operate the unit with this mode, additional setting of "Continuous Demand Setting" or
external input by external control adapter is required.
Demand 1
Demand 2
5.3

Heating Operation Prohibition

Heating operation is prohibited above 24°C ambient temperature.
132
Operating method
REYQ8 ~ 16PY1
REYQ18 ~ 48PY1
Reset the remote controller. (Press the RUN/STOP button for 4 seconds or more.)
Disable the defective outdoor unit from operating, and then only operate other outdoor
units.
(On systems with 1 outdoor unit, this emergency operation is not available.)
Make setting of the compressor, "the operation of which is to be disabled", in field setting
mode (setting mode 2).
(For detail of the setting method, refer to page 204.)
Disable the compressor with "operation disable setting" made from operating and only
operate other compressors.
(On the system with 1 compressor "REYQ8PY1", this emergency operation is not
available.)
Set item
Condition
Mode 1
Mode 2
Mode 3
(1) Emergency operation with
remote controller reset
(Auto backup operation)
Backup operation by the
indoor unit
The compressor operates at approx. 60% or less of rating.
The compressor operates at approx. 70% or less of rating.
The compressor operates at approx. 80% or less of rating.
The compressor operates at approx. 40% or less of rating.
Si37-701
(2) Emergency operation with
outdoor unit PC board setting
(Manual backup operation)
Backup operation by the
compressor
Backup operation by the
outdoor unit
Content
Function