Malfunction Of Transmission Between Centralized Controller And Indoor Unit; Centralized Controller And Indoor Unit - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
UE
3.55 "
"
Malfunction of Transmission between Centralized
Controller and Indoor Unit
UE
Remote
Controller
Display
Applicable
All models of indoor units
Centralized controller
Models
Schedule timer
Method of
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
330
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
(or disconnection of connector for independent / combined use changeover switch.)
Failure of PC board for central remote controller
Defect of indoor unit PC board
Intelligent Touch Controller
Si37-701
Troubleshooting