Si37-701
(13) Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting Table
(14) Operation of Downward Flow Flap: Yes/No
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
(15) Setting of Air Flow Direction Adjustment Range
Make the following air flow direction setting according to the respective purpose.
Setting Table
(16) Setting of the Static Pressure Selection (for FXDQ model)
(17) Humidification When Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction temperature is 20ºC or
above and turns OFF the humidifier if suction temperature is 18ºC or below when the heating
thermostat is OFF.
Test Operation
Mode No.
First Code No.
13 (23)
1
Mode No.
First Code No.
13 (23)
Mode No.
13 (23)
Some indoor unit models are not equipped with draft prevention (upward) function.
Model No.
13 (23)
Mode No.
15 (25)
Second Code
No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Second Code No.
3
First Code No.
Second Code No.
4
First Code No.
Second Code No.
5
First Code No.
Second Code No.
1
Setting
Setting
01
Down-flow operation: Yes
02
Down-flow operation: No
Setting
Upward (Draft
01
prevention)
02
Standard
Downward (Ceiling
03
soiling prevention)
External static pressure
01
Standard (15Pa)
02
High static pressure (44Pa)
Setting
01
02
Setting of humidifier
Field Setting
177