Si37-701
JA
3.33 "
" Outdoor Unit:
JA
Remote
Controller
Display
Applicable
REYQ8P~48P
Models
Method of
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Detection
Malfunction
When the high pressure sensor is short circuit or open circuit.
(Not less than 4.22MPa, or 0.01MPa and below)
Decision
Conditions
Supposed
Causes
Troubleshooting
Malfunction of High Pressure Sensor
Defect of high pressure sensor system
Connection of low pressure sensor with wrong connection.
Defect of outdoor unit PC board.
Defective connection of high pressure sensor
Troubleshooting by Indication on the Remote Controller
279