Special Control
3.5

Pump-down Residual Operation

3.5.1 Pump-down Residual Operation in Cooling Operation
If the liquid refrigerant stays in the Evaporator at the startup of a compressor, this liquid refrigerant enters the
compressor, thus resulting in diluted oil in the compressor and then degraded lubrication performance.
Consequently, in order to recover the refrigerant in the Evaporator while the compressor stops, the pump-down residual
operation is conducted.
Actuator
Compressor 1
Compressor 2
Compressor 3
Outdoor unit fan 1
Outdoor unit fan 2
Electronic expansion valve (Main) EVM
Electronic expansion valve
(Supercooling)
Electronic expansion valve
(Refrigerant charge)
Four way valve (Heat exchanger
switch)
Four way valve (High/low pressure
gas pipe switch)
Solenoid valve (Main bypass)
Solenoid valve (Hot gas)
Solenoid valve (Refrigerant
regulator liquid pipe )
Solenoid valve (Refrigerant
regulator gas vent pipe)
Solenoid valve (Refrigerant
regulator exhaust pipe)
Solenoid valve (Refrigerant
regulator discharge pipe)
Ending conditions
* Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
120
Elect.
symbol
Symbol
REYQ
REMQ
M1C
M1C
M2C
M2C
124 Hz+OFF+OFF
M3C
M3C
M1F
M1F
Fan control
M2F
M2F
Y1E
Y1E
1375 pls
Y3E
Y2E
EVT
Y3E
0 pls
Y5E
EVJ
Y4E
Y2E
80 pls
Y2S
20SA
Y3S
OFF
Y9S
20SB
Y8S
Y2S
ON
Y5S
SVE
Y10S Y6S
ON
SVP
Y4S
Y5S
OFF
SVL
Y3S
Y4S
OFF
SVG
Y1S
Y1S
OFF
SVO
Y7S
Y7S
OFF
SVT
Y6S
Y8S
OFF
or
Master unit operation
• 5 min.
• Pe_min<0.49 MPa ∗
• Pc_max<2.94 MPa ∗
• Master unit Tdi>110°C
• Master unit Tp>125°C
Si37-701
Slave unit operation
OFF
Fan control
1375 pls
0 pls
80 pls
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents