Outdoor Air - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
H9
3.24 "
" Outdoor Unit:

Outdoor Air

H9
Remote
Controller
Display
Applicable
REYQ8P~48P
Models
Method of
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Detection
Malfunction
When the outside air temperature thermistor has short circuit or open circuit.
Decision
Conditions
Supposed
Causes
Troubleshooting
270
Malfunction of Thermistor (R1T) for
Defective thermistor connection
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Confirm which thermistor is
abnormal using outdoor unit
"monitor mode".
(Refer to P226~227)
Connector is
connected to X18A of
outdoor PC board
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(1.8kΩ to
800kΩ)
YES
Refer to "Thermistor Resistance / Temperature Characteristics" table on P417.
NO
NO
Si37-701
Connect the connector and turn on
again.
Replace the thermistor (R1T)
Replace outdoor unit PC board
(A1P).
Troubleshooting
(V3070)