5. Troubleshooting (Inverter)
5.1
Outdoor Unit: Malfunction of Inverter Radiating Fin Temperature Rise
L4
Remote Controller
Display
Supposed Causes
Troubleshooting
Troubleshooting R-407C PLUS Series
Actuation of fin thermal (Actuates at min. 90˚C and resets at max. 80˚C)
Defect of inverter PC board
Defect of fin thermistor
Temperature
of the radiator fin rises.
Actuates at min. 90 ˚C
Resets at max.
80 ˚C
NO
Characteristic
check of the radiator fin
thermistor (Refer to thermistor
characteristics
table.)
Normal
Is reset possible?
YES
YES
Abnormal
NO
Troubleshooting (Inverter)
Defect of power unit radiation.
• Intake port is clogged
• Radiator fin is dirty
• Outdoor temperature is high
Replace the thermistor.
Replace the inverter unit.
Reset and operate.