Malfunction Of Transmission Between Indoor Units; U4 " Malfunction Of Transmission Between Indoor Units - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Si37-701
U4
3.48 "
"

Malfunction of Transmission between Indoor Units

U4
Remote
Controller
Display
Applicable
All model of indoor unit
Models
REYQ8P~48P
Method of
Check if the transmission between indoor unit and outdoor unit is correctly executed using
microcomputer.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
Troubleshooting
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address doesn't match
Defect of indoor unit PC board
Defect of outdoor unit PC board
Troubleshooting by Indication on the Remote Controller