Daikin VRV III REYQ8PY1 Service Manual page 185

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Field Setting
3.1.6 Detailed Explanation of Setting Modes
(1)
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Setting
Contamination Light
Contamination Heavy
(2) Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
(3) Selection of Thermistor
Select the thermistor to control room temperature.
The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and remote controller thermistor.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the remote
controller thermistor.
(4) "Filter Cleaning" Displayed or Not Displayed
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
(5) Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided.
Output signal is output between terminals K1 and K2 of "customized wiring adapter," an optional
accessory.
174
Filter Specs.
Mode No.
Setting Switch No.
10 (20)
Mode No.
First Code No.
10 (20)
2
Mode No.
First Code No.
10 (20)
Mode No.
First Code No.
12 (22)
0
Standard
Long Life
200 hrs.
2,500 hrs.
100 hrs.
1,250 hrs.
Setting Position No.
1
Second Code No. Thermistor that controls room temperature
Indoor air thermistor for remote controller
01
and suction air thermistor for indoor unit
02
Suction air thermistor for indoor unit
03
Thermistor for remote controller
Second Code No.
3
Second Code No.
Indoor unit thermostat ON/OFF signal is
01
provided.
Output linked with "Start/Stop" of remote
03
controller is provided.
In case of "Malfunction Display" appears
04
on the remote controller, output is
provided.
Ultra Long Life Filter
10,000 hrs.
5,000 hrs.
Setting
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
"Filter Cleaning" display
01
Display
02
No display
Remarks
Test Operation
Si37-701

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents