Standby - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Special Control
3.6

Standby

3.6.1
Restart Standby
Used to forcedly stop the compressor for a period of 2 minutes, in order to prevent the frequent ON/OFF of the
compressor and equalize the pressure within the refrigerant system.
Actuator
Compressor1
Compressor2
Compressor3
Outdoor unit fan1
Outdoor unit fan2
Electronic expansion valve
(Main)
Electronic expansion valve
(Supercooling)
Electronic expansion valve
(Refrigerant charge)
Four way valve (Heat
exchanger switch)
Four way valve (High/low
pressure gas pipe switch)
Solenoid valve (Main bypass) SVE
Solenoid valve (Hot gas)
Solenoid valve (Refrigerant
regulator liquid pipe )
Solenoid valve (Refrigerant
regulator gas vent pipe)
Solenoid valve (Refrigerant
regulator exhaust pipe)
Solenoid valve (Refrigerant
regulator discharge pipe)
Ending conditions
3.6.2 Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this mode is used to control
the crankcase heater.
Crankcase heater
122
Elect.
symbol
Symbol
REYQ8~16P
REYQ
REMQ
M1C M1C
M2C M2C
M3C M3C
Ta>30°C: STEP4
MF1
MF1
Ta≤30°C: OFF
Ta>30°C: STEP4
MF2
MF2
Ta≤30°C: OFF
Y1E
EVM
Y1E
Y3E
Y2E
EVT
Y3E
Y5E
EVJ
Y4E
Y2E
Y2S
20SA
Y3S
Y9S
20SB
Y8S
Y2S
Y5S
Y6S
Y10S
SVP
Y4S
Y5S
SVL
Y3S
Y4S
SVG
Y1S
Y1S
SVO
Y7S
Y7S
SVT
Y6S
Y8S
Discharge pipe
temperature < 70 ˚C
OFF
Discharge pipe
temperature > 75 ˚C
Operation
REMQ8P
OFF
OFF
OFF
Ta>30°C: STEP4
Ta≤30°C: OFF
Crankcase heater
REMQ10•12P
REMQ14•16P
OFF
OFF
Ta>30°C: STEP4
Ta>30°C: STEP4
Ta≤30°C: OFF
Ta≤30°C: OFF
Ta>30°C: STEP4
Ta≤30°C: OFF
0 pls
0 pls
80 pls
Holds
Holds
OFF
OFF
OFF
OFF
OFF
OFF
2 min.
ON
Si37-701
OFF
OFF
OFF
Function