Si37-701
E4
3.15 "
" Outdoor Unit:
E4
Remote
Controller
Display
Applicable
REYQ8P~48P
Models
Method of
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Detection
Malfunction
Error is generated when the low pressure is dropped under compressor operation.
Operating pressure:0.07MPa
Decision
Conditions
Supposed
Causes
Troubleshooting
Actuation of Low Pressure Sensor
Abnormal drop of low pressure (Lower than 0.07MPa)
Defect of low pressure sensor
Defect of outdoor unit PC board
Stop valve is not opened.
Troubleshooting by Indication on the Remote Controller
253