A9 " Indoor Unit: Malfunction Of Electronic Expansion Valve Coil - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
A9
"
" Indoor Unit:
Valve Coil
A9
Remote
Controller
Display
Applicable
Indoor units except FXFQ models
Models
Method of
Check coil condition of electronic expansion valve by using microcomputer.
Malfunction
Detection
Malfunction
Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Decision
Conditions
Supposed
Causes
242
Malfunction of Electronic Expansion
Defective drive of electronic expansion valve
Defective PC board of indoor unit
Defective relay cables
Si37-701