Daikin VRV III REYQ8PY1 Service Manual page 48

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Si37-701
Ceiling Mounted Built-in Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number of
Units
Fan
Air Flow Rate (H/L)
4 External static
pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Mass (Weight)
6 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel Color
Panel
Dimensions: (H×W×D)
(Option)
Weight
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
Specifications
FXSQ80MVE
kcal/h
8,000
Btu/h
31,700
kW
9.3
kW
9.0
kcal/h
8,600
Btu/h
34,100
kW
10.0
Galvanized Steel Plate
mm
300×1,400×800
mm
3×14×1.75
0.338
3D18H2A
Sirocco Fan
W
225×1
l/s
450/358
m³/min
27/21.5
cfm
953/759
Pa
113-82
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
mm
9.5 (Flare Connection)
φ
mm
15.9 (Flare Connection)
VP25
mm
(External Dia. 32 Internal Dia. 25)
kg
51
220V
43/37
dBA
240V
45/39
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS125DJW1
White (10Y9/0.5)
mm
55×1,500×500
kg
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
means
"High static pressure-Standard".
values are normally somewhat higher during actual operation as a result of ambient conditions.
FXSQ100MVE
10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
300×1,400×800
3×14×1.75
0.338
3D18H2A
Sirocco Fan
225×1
466/366
28/22
988/777
107-75
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
51
43/37
45/39
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS125DJW1
White (10Y9/0.5)
55×1,500×500
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
C: 3D039431
Specifications
FXSQ125MVE
12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
300×1,400×800
3×14×1.75
0.338
3D18H2A
Sirocco Fan
225×1
633/466
38/28
1,341/988
78-39
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
52
46/41
48/43
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS125DJW1
White (10Y9/0.5)
55×1,500×500
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
37

Hide quick links:

Advertisement

Table of Contents
loading