Troubleshooting (Op: Central Remote Controller); Pc Board Defect; M1 " Pc Board Defect - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Troubleshooting (OP: Central Remote Controller)

4.

Troubleshooting (OP: Central Remote Controller)

M1
"
"
4.1

PC Board Defect

M1
Remote
Controller
Display
Applicable
Central remote controller
Schedule timer
Models
Method of
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction
Detection
Malfunction
When + polarity and - polarity are detected at the same time.
Decision
Conditions
Supposed
Causes
Troubleshooting
Replace the central remote controller.
336
Defect of central remote controller PC board
Defect of Intelligent Touch Controller PC board
Defect of Schedule timer PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn ON the power supply of
the central equipment
M1
with
displayed once again.
M1
Is the
displayed again?
M1
Without
displayed
Intelligent Touch Controller
M1
With
displayed
Si37-701
Replace the central
equipment.
Central equipment: Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents