Si37-701
Evaporating outdoor unit actuator
Compressor 1
Compressor 2
Compressor 3
Outdoor unit fan 1
Outdoor unit fan 2
Four way valve (for heat changer
selection)
Four way valve (for high- and low-
pressure gas pipe selection)
Electronic expansion valve (main)
Electronic expansion valve
(subcooling)
Electronic expansion valve
(refilling refrigerant)
Solenoid valve (main bypass)
Solenoid valve (hot gas)
Solenoid valve (liquid pipe of
refrigerant regulator)
Solenoid valve (gas discharge
pipe of refrigerant regulator)
Solenoid valve (drain pipe of
refrigerant regulator)
Solenoid valve (discharge pipe of
refrigerant regulator)
Cooling indoor unit actuator
Fan
Motorized valve
Heating indoor unit actuator
Fan
Motorized valve
Cooling BS unit actuator
Electronic expansion vale (EVH)
Electronic expansion vale (EVL)
Electronic expansion vale (EVHS)
Electronic expansion vale (EVLS)
Electronic expansion vale (EVSC)
Heating BS unit actuator
Electronic expansion vale (EVH)
Electronic expansion vale (EVL)
Electronic expansion vale (EVHS)
Electronic expansion vale (EVLS)
Electronic expansion vale (EVSC)
Function
Elect. symbol
Symbol
REYQ REMQ
M1C
M1C REYQ8•10•12P: 232Hz+ON
REYQ14•16P: 232Hz+232Hz
M2C
M2C
REMQ8P: 210Hz
REMQ10•12P: 210Hz+ON
REMQ14•16P: 210Hz+ON+ON
M3C
M3C
M1F
M1F
Fan control
M2F
M2F
Y2S
20SA
Y3S
ON
Y9S
20SB
Y8S
Y2S
Holds
Y1E
EVM
Y1E
PI control
Y3E
Y2E
EVT
Y3E
SH control
Y5E
EVJ
Y4E
Y2E
80pls
Y5S
SVE
Y6S
OFF
Y10S
SVP
Y4S
Y5S
OFF
SVL
Y3S
Y4S
0pls
SVG
Y1S
Y1S
0pls
SVO
Y7S
Y7S
0pls
SVT
Y6S
Y8S
0pls
Thermo ON unit
Unit not in operation
Thermo OFF unit
Thermo ON unit
Unit not in operation
Thermo OFF unit
Thermo ON unit
Unit not in operation
Thermo OFF unit
Thermo ON unit
Unit not in operation
Thermo OFF unit
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Y1E
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Y1E
Defrost operation
Upper limit 124Hz (STD Holds)
REYP400•480A: 232Hz+232Hz
REMP224A: 210Hz
REMP280•335A: 210Hz+ON
REMP400•450A:
210Hz+ON+ON
Fan control
ON
Holds
PI control
0pls
80pls
OFF
OFF
0pls
0pls
0pls
0pls
Defrost operation
Remote controller setting
Remote controller setting
Normal opening degree
Defrost operation
REYQ
OFF
OFF
OFF
0pls
0pls
0pls
Defrost operation
Defrost operation
0pls (REYQ8~16P) 60pls (REMQ8~16P)
0pls (PI control for cool/heat concurrent operation)
Special Control
Operation after defrost
OFF
0pls
0pls
REMQ
LL
LL
LL
224pls
0pls
224pls
0pls
760pls
0pls
480pls
0pls
760pls
0pls
60pls
119