C9 " Indoor Unit: Malfunction Of Thermistor (R1T) For Suction Air - Daikin VRV III REYQ8PY1 Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
C9
3.11 "
" Indoor Unit:
Suction Air
C9
Remote
Controller
Display
Applicable
AII indoor unit models
Models
Method of
Malfunction detection is carried out by temperature detected by suction air temperature
thermistor.
Malfunction
Detection
Malfunction
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running.
Decision
Conditions
Supposed
Causes
Troubleshooting
248
Malfunction of Thermistor (R1T) for
Defect of indoor unit thermistor (R1T) for air inlet
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Remove the thermistor from
the indoor unit PC board, and
then insert it again.
Is the
thermistor normal?
NO
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
5 kΩ to 90 kΩ
YES
Refer to "Thermistor Resistance / Temperature Characteristics" table on P417.
YES
NO
Si37-701
Normal (The malfunction is
caused by faulty contact.)
Replace the thermistor (R1T).
Replace the indoor unit PC board.