Setup And Configuration - Dhw Tank; Dhw Pump For Instant Hot Water - Daikin Altherma 3 M Installer's Reference Manual

Hide thumbs Also See for Altherma 3 M:
Table of Contents

Advertisement

6
|
Application guidelines
6.4.3 Setup and configuration – DHW tank

6.4.4 DHW pump for instant hot water

Installer reference guide
50
When the heat pump produces domestic hot water, it cannot heat up a space. In
case you need domestic hot water and space heating at the same, we
recommend to produce the domestic hot water during the night when there is
lower space heating demand.
For large DHW consumptions, you can heat up the DHW tank several times
during the day.
To heat up the DHW tank to the desired DHW tank temperature, you can use the
following energy sources:
-
Thermodynamic cycle of the heat pump
-
Electrical booster heater
For more information about:
-
Optimising the energy consumption for producing domestic hot water, see
"11 Configuration" [
-
Connecting the electrical wiring of the standalone DHW tank to the outdoor
unit, see the installation manual of the DHW tank, and the addendum book for
optional equipment.
-
Connecting the water piping of the standalone DHW tank to the outdoor unit,
see the installation manual of the DHW tank.
-
Optimising the minimum water volume requirement by using the tank
preheating function:
See
"To check the water volume and flow
requirements.
For stainless steel tanks (EKHWS*D*), the additional components described in
"DHW pump for tank
For polypropylene tanks (EKHWP*), the booster heater option (EKBH3S) must
be installed.
INFORMATION
This topic shows an application example in case of stainless steel tanks (EKHWS*D*).
Setup
a
b
a DHW tank
4
 123].
4
preheating" [
 52] must be installed.
d
e
f
M
4
rate"  [
  76] for water circuit
c
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06