Festo CPX DE Series Manual page 158

Digital i/o modules, sub-bases and pneumatic interfaces
Hide thumbs Also See for CPX DE Series:
Table of Contents

Advertisement

5. CPX pneumatic interfaces
Midi/Maxi, CPA or
VTSA pneumatics
Fault LED
Sequence
(red)
ON
OFF
LED is off
ON
OFF
LED lights
LED lights
Tab. 5/10: Fault LED for pneumatic interfaces Midi/Maxi, CPA or VTSA pneumatics
5−22
Fault LED
The red fault LED of these pneumatic interfaces indicates
the faults of the pneumatic interface depending on the
parameterization.
Status
Faultless operation
Fault in load voltage for valves
Load voltage for the valves (V
missing or too low.
Fault short circuit at valve
Short circuit/overload at valve
Wire fracture fault
Monitoring the residual current of
the valve solenoid coils (open load,
only active with 0−signal).
Only relevant for CPA or VTSA pneu
matics.
The fault indicated by the red fault LED is transmitted by the
pneumatic interface to the field bus node (unless parameter
ized otherwise).
Status LEDs of the valve solenoid coils
The yellow status LEDs on the valve solenoid coils indicate
the status of the relevant output (see appropriate pneumatics
manual).
Fault
Fault
number
treatment
None
5
See section
)
5.6.1, Tab. 5/9
VAL
11
13
Festo P.BE−CPX−EA−E N en 0804g

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents