User code for arming/disarming report
Arming/Disarming Method
Key-switch zone
Single button arming
Remote telephone arming
Remote PC arming
Tamper Status – Tamper Report
If a tamper occurs, it will send the tamper alarm report to configured destinations.
Zone Status – Bypass Report
A zone is bypassed when it is manually isolated. A Zone Bypass Report is sent at the end of
Exit Time for any zone that was manually isolated. A 24-Hour Zone sends a Zone Bypass
Report when the zone is selected to be isolated manually.A Zone Bypass Restore Report is
sent when the system is disarmed. All bypassed zones are automatically cleared when the
system is disarmed.
Zone Status – Fault Report
A zone fault report is sent when the system is unsealed at the end of Exit Time and the zone is
automatically bypassed. A zone fault report is not sent when a 24-Hour zone is unsealed after
the Exit Time. A Fault Restore Report is sent for non-24-Hourr Zones when the zone is
resealed or the next time the system is disarmed (whichever happens first). A 24-Hour Zone
sends a restore signal only when it is resealed.
Zone Status – Alarm Restore Report
An alarm restore Report is sent to the base station destination when the alarm is restored
from STAY/AWAY Mode.If a non-24-Hour zone is not restored when the system is disarmed,
the system automatically sends a Zone Restore Report for that zone. All 24-Hour zones send a
Zone Restore Report only when the zone is restored.
Zone Status - Arm/Disarm Report
A Disarm Report is sent to the base station destination when the system is disarmed from
STAY/AWAY Mode. An Arm Report is sent at the end of Exit Time when the system is armed in
STAY/AWAY Mode.
Keypad – Duress Report
A Duress Report is sent to the base station destination when 0 is added to the end of any valid
User Code used to disarm the system. This alarm is always silent. A Duress Alarm can be
triggered during Exit Time (in other words, if the system is armed and then disarmed by
adding 0 to the end of the User Code before Exit Time expires, a Duress Report is
transmitted). Adding 0 to the end of a User Code when arming the system does not cause a
Duress Alarm.
Keypad – Panic Report
A Panic Alarm Report is sent to the base station destination when a user presses either [1]
and [3] or [*] and [#] at the same time.Restore Reports are not sent for this event.
Keypad – Fire Report
A Fire Alarm Report is sent to the base station destination when a user presses [4] and [6] at
the same time.Restore Reports are not sent for this event.
Bosch Sicherheitssysteme GmbH
AWAY/STAY arming
User 17 (Only AWAY arming)
User 18
User 19
User 20
Installation Manual
System Informations 2 | en
Disarming
User 17
NA
NA
NA
F.01U.241.127 | V4 | 2011.12