The pulse is used for both panel and remote receiver to know whether the network
connection is good or not. Each time when a pulse is due, the control panel will send a pulse
message. The pulse time range is from 1 to 999 minutes. For time less than 3 digits, use 0 to
fulfill.
Contact your central monitoring station for the correct setting.
7.7.3

Report Transmission Sequence

(Refer to Section 10.2.1 Report Options, page 79 and Section 10.4 Zone Programming, page 82).
If the event has disabled the report (option 0), no report is sent out. The domestic alarm is set
as configured.If the report has any destination to contact the panel (option 1, 2, 3, 4, 5, 6, 7),
It will call the related destination by related reporting format type and subscriber ID Number.
Attempt rules:
1.
2.
3.
4.
7.7.4

Receiver 1 - 4 Transmission Format

(Refer to Section 10.1.1 Receiver Parameters, page 78). You can select the transmission format
with location options to specify how to transmit the information to the base station receiver.
If Contact ID or CFSK format is selected, the information is transmitted by telephone line; if
Bosch Network is selected, then it is connected with B420/DX4020 or ITS-DX4020G GPRS.
Transmission format is defaulted as Contact ID.
Bosch Sicherheitssysteme GmbH
Attempt times and duration
The attempt sequency is destination 1, 2, 3, 4 and domestic destination. Some disabled
destinations will be ignored.
When a new report needs to be sent out, the system will send the report based on the
report destination programming list.
For each enabled destination, the panel will retry sending the report to it till the report
has been sent to the destination, or till the report buffer overflows and the old report is
replaced by new incoming reports.
For each enabled destination, the retry interval time between two retries is 15 seconds
for the 1st retry to 4th retry, and the retry interval time between two retries is 10 minutes
for the 5th retry to 8th retry, after the 8th retry the retry interval time between two
retries is 60 minutes.
For all enabled destinations (except domestic destinations), the waiting time for next
retry would be cleared to zero as long as there is a new report.
Attempt Priority
The attempt priority is destination 1, 2, 3, 4, Domestic. The disabled destinations will be
ignored.
Communication Fail Fault
If the attempt times for one destination reaches 4, the system will cause the
communication fail fault for this destination.
Backup Destination Process
If the destination failed for 4 attempts, the pending reports will switch between primary/
backup destinations in this group.If the report option selects 6, only one group: 1, 2, 3, 4
destinations.If the report option selects 7, there are two groups: group 1 is 1, 2
destinations. Group 2 is 3, 4 destinations.The system can save up to a maximum of 50 un-
reported events. If the un-reported events are more than 50, it will delete earlier events
and only save the last 50 events in the buffer to send out.
Installation Manual
System Informations 1 | en
F.01U.241.127 | V4 | 2011.12