76
en | Technical Data
Aux (+12V/GND) Output:
Option Bus:
RF Power Output
Panel PCB
Battery:
Certification:
Keypads:
IUI-AMAX-LED8 (8Zone LED Keypad)
Relative Humidity:
Operating Temperature:
Input Voltage range:
Current Consumption
Cable requirements:
EN type:
IUI-AMAX-LCD8 (8Zone LCD Keypad)
Relative Humidity:
Operating Temperature:
Input Voltage range:
Current Consumption
Cable requirements:
EN type:
F.01U.241.127 | V4 | 2011.12
–
Nominal Output Voltage under AC line input: 13,5 VDC +3%
/ -5%
–
Output Voltage Range under AC line input: 12,82 VDC to
13,9 VDC
–
500mA maximum
–
Vpp (max) 675mV
–
Nominal Output Voltage under AC line input: 13,5 VDC +3%
/ -5%
–
Output Voltage Range under AC line input: 12,82 VDC to
13,9 VDC
–
500mA maximum
–
5VDC / 100mA maximum
–
Quiescent current maximum 100mA
–
D126 (12V/7 Ah) sealed, lead acid rechargeable
–
Low battery condition is below 11,8 VDC
–
Minimum battery condition is 10,8VDC
–
Maximum auxiliary current to recharge standby battery to
80% within 72h: 12 V/7 Ah Battery: 550mA
–
EN 50131-3 GRADE 2 ENV-II = ENVIRONMENTAL GRADE II
–
10%-95%
–
-10°C - +55°C
–
10VDC - 14VDC
–
standby 24mA
–
maximum 50mA
–
four wire, unshielded and shielded 0,6-0,8mm
–
maximum length 150m
–
B
–
10%-95%
–
-10°C - +55°C
–
10VDC - 14VDC
–
standby 18mA
–
maximum 60mA
–
four wire, unshielded and shielded 0,6-0,8mm
–
maximum length 150m
–
B
Installation Manual
AMAX panel 2000 / AMAX panel 2000 EN
Bosch Sicherheitssysteme GmbH