en | Technical Data
Aux (+12V/GND) Output:
Option Bus:
RF Power Output
Panel PCB
Battery:
Certification:
Keypads:
IUI-AMAX-LED8 (8Zone LED Keypad)
Relative Humidity:
Operating Temperature:
Input Voltage range:
Current Consumption
Cable requirements:
EN type:
IUI-AMAX-LCD8 (8Zone LCD Keypad)
Relative Humidity:
Operating Temperature:
Input Voltage range:
Current Consumption
Cable requirements:
EN type:
F.01U.241.127 | V4 | 2011.12
Nominal Output Voltage under AC line input: 13,5 VDC +3%
/ -5%
Output Voltage Range under AC line input: 12,82 VDC to
13,9 VDC
500mA maximum
Vpp (max) 675mV
Nominal Output Voltage under AC line input: 13,5 VDC +3%
/ -5%
Output Voltage Range under AC line input: 12,82 VDC to
13,9 VDC
500mA maximum
5VDC / 100mA maximum
Quiescent current maximum 100mA
D126 (12V/7 Ah) sealed, lead acid rechargeable
Low battery condition is below 11,8 VDC
Minimum battery condition is 10,8VDC
Maximum auxiliary current to recharge standby battery to
80% within 72h: 12 V/7 Ah Battery: 550mA
EN 50131-3 GRADE 2 ENV-II = ENVIRONMENTAL GRADE II
10%-95%
-10°C - +55°C
10VDC - 14VDC
standby 24mA
maximum 50mA
four wire, unshielded and shielded 0,6-0,8mm
maximum length 150m
B
10%-95%
-10°C - +55°C
10VDC - 14VDC
standby 18mA
maximum 60mA
four wire, unshielded and shielded 0,6-0,8mm
maximum length 150m