en | Troubleshooting
Trouble
Battery fault still
indicates after replaced
with new battery.
Control Panel does not
dial.
No remote arming
function.
No RPS software
function.
Abnormal in PSTN/
Domestic dialling
communicaiton.
F.01U.241.127 | V4 | 2011.12
Causes & Measures
System test the battery each time arming or every time set
in location 191. Only after testing the battery fault can be
cleared away.
Voltage of the new battery reaches the normal value after it
is charged for some time.
Check if the dialing function is switched off in
communication programming (Telephone number and
transmission format need to be programmed).
Check if the function is switched off (Do not set Location
152 and 153 as 0).
Check if the function is switched off (Do not set Location
152 and 153 as 0).
When extention system is used in telephone network,
dialing delay needs to be added in programming.
Network supports the ADSL at the same time, the control
panel needs to be connected through the ADSL filter .