Dry Contact Card - Huawei UPS5000-E Series User Manual

50 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Specifications

2.3.4.3 Dry contact card

Appearance
Figure 2-20 Dry contact card
Table 2-6 Ports on the dry contact card
Silk Screen
BTG
0V
GEN
0V
BCB_OL
BCB_STA
BCB_DRV
BCB_0V
EPO_NO
Issue 11 (2019-12-20)
Hot-swappable
1 U high
Description
Port for detecting battery
grounding faults
Port for signal ground
Port for detecting diesel
generator (D.G.) mode
Port for signal ground
Port for detecting the BCB
box
Port for monitoring the
battery switch
Controls battery circuit
breaker trip. When the
voltage is +12 V, the circuit
breaker trips.
Port for signal ground
Emergency power-off (EPO)
port
Copyright © Huawei Technologies Co., Ltd.
Status
Connected: battery
grounding fault
Disconnected: no
battery grounding
fault
Connected: D.G.
mode
Disconnected:
non-D.G. mode
Grounded: BCB
box connected
Disconnected:
BCB box not
connected
Connected: battery
switch ON
Disconnected:
battery switch
OFF
0 V: battery switch
not tripped
12 V: battery
switch tripped
If the normally open
(NO) port is
2 Overview
Initial Status
Disconnected
Disconnected
Grounded
Disconnected
0 V
Disconnected
36

Hide quick links:

Advertisement

Table of Contents
loading