UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Figure 3-39 Ground cable connection
Step 4 Route power cables.
Issue 11 (2019-12-20)
: Internal equipotential connection
: Protection ground
Dual mains
Remove the copper bars between mains and bypass input terminals.
Figure 3-40
shows power cables routed from the bottom by removing small covers, as an