Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Issue 11 (2019-12-20)
Description
recovery time.
If Capacitor failure detection is
set to Enable, the power module
(power unit) performs inverter
capacitor fault detection based on
the settings of Capacitor failure
detection upper limit and
Capacitor failure detection
lower limit. If the power module
determines that the inverter
capacitor is faulty, it shuts down
the inverter to prevent the fault
from expanding.
Description
Specifies whether to start bypass
mode when overtemperature
occurs.
Enable or disable the light load
bypass current imbalance alarm.
If this parameter is set to Enable,
the load is light (less than 30%
load), and the load rate of a
certain rack is less than 10%, the
system will generate a bypass
current imbalance alarm and
cannot enter the ECO mode. If
this parameter is set to Disable,
the preceding detection is not
performed. Whether the bypass
current is imbalanced does not
affect the ECO bypass mode.